Monthly temperature checks are the backbone of legionella control. Doing them at the right outlets and in the right way is what makes them count.
By the Germ3 Water team. Updated 20 October 2026.
What a sentinel outlet is
A sentinel outlet is a tap or shower chosen to represent part of your water system. They are usually the first and last outlets on each hot and cold water circuit. That means the nearest and the furthest from the calorifier or tank.
If the furthest outlet reaches the right temperature in time the rest of the circuit almost certainly does too. Your risk assessment should list your sentinel outlets by location.
The targets
For most hot and cold water systems HSG274 Part 2 sets these monthly targets:
- Hot water should reach at least 50°C within one minute. In healthcare it should reach 55°C.
- Cold water should fall below 20°C within two minutes.
Calorifier flow and return temperatures are checked monthly too. Stored hot water should be at least 60°C.
How to take a reading
- Use a calibrated digital thermometer with a probe.
- Turn the tap on fully and start a timer.
- Hold the probe in the flow of water.
- Read the temperature at one minute for hot or two minutes for cold.
- Write the reading and the time taken in your logbook.
Do it the same way every month. Readings taken in different ways are hard to compare.
Where TMVs fit in
A thermostatic mixing valve blends hot and cold water to a safe temperature for washing. That protects people from scalding. It also means the water after the valve sits at a temperature where legionella can grow.
Your checks at a TMV outlet tell you the valve is working. They do not tell you the hot supply is hot enough. Where you can check the hot water going into the valve as well. Keep the pipe run after the valve as short as possible.
When a reading is out of range
Record it and tell the responsible person the same day. Check it again. If it is still out of range the cause needs finding. That may be a calorifier setting or a failed valve. It may also be a pipe run that needs insulating.
Questions
Common questions
How many sentinel outlets do I need?
At least the first and last outlet on each hot and cold circuit. Your risk assessment should set the number for your building.
Can I use any thermometer?
Use a calibrated digital thermometer with a probe. Check its calibration regularly so your readings can be trusted.
Do TMVs need monthly checks?
Check the outlet temperature as your scheme sets out. TMVs also need servicing and a fail safe test at least once a year.